RE-2Y(St)H-TP

Stranded electrolytic copper conductor
Black and white, number coded Polyethylene insulation
Polyester tape
Tinned copper earthing wire, Al/PET tape
Black HFFR sheath
This cable is used in chemical and petrochemical industry, powerplants, gas stations, water transportation systems,  instrumentation control and data processes, analog and digital signal transmission, dry or wet places.
Category: Tags: ,
  • Description

    Product Description

    İletken
    Kesiti
    İletken
    Direnci
    Ω/km (20 °C)
    İzolasyon
    Direnci
    MΩ/km (20 °C)
    Efektif
    Kapasite
    pF/m
    Endüktans/
    Direnç Oranı
    nH/Ω
    Akım Taşıma
    Kapasitesi
    A
    Çalışma
    Voltajı
    V DC
    Test Voltajı
    V (DC.
    1 dakika)
    Cross
    Section
    Conductor
    Resistance
    Ω/km (20 °C)
    Insulation
    Resistance
    MΩ/km (20 °C)
    Mutual
    Capacitance
    pF/m
    Inductance/
    Resistance
    Ratio nH/Ω
    Current
    Carrying
    Capacity A
    Operating
    Voltage
    V DC
    Test Voltage
    V (DC.
    1 minute)
    0.50 mm² 36 5000 65 25 6 300/500 2000
    0.75 mm² 24,5 5000 65 25 13 300/500 2000
    1.00 mm² 18,1 5000 65 25 16 300/500 2000
    1.30 mm² 13,9 5000 75 40 18 300/500 2000
    1.5 mm² 12,1 5000 75 40 20 300/500 2000
    Bükülme Yarıçapı Sıcaklık Aralığı Duman Yoğunluk Testi Korozif Gaz Testi Halojensizlik Testi Alev Yayılma Testi
    Bending Radius Temperature Range Smoke Density Test Corrosive Gas Test Halogen-free Test Flame Propagation Test
    7.5xD mm -30°C~+70°C IEC 61034-2,
    VDE 0482-1034-2,
    EN 61034-2,
    BS EN 61034-2
    IEC 60754-2,
    VDE 0482-267-2-3,
    EN 50267-2-3,
    BS EN 50267-2-3
    IEC 60754-1,
    VDE 0482-267-2-1,
    EN 50267-2-1,
    BS EN 50267-2-1
    IEC 60332-3-24,
    EN 60332-3-24,
    BS EN 60332-3-24,
    VDE 0482-332-3-31
  • Additional information

    Additional Information

    Certificates

    Trial