RE-Y(St)Y-TP

Stranded electrolytic copper conductor
Black and white, number coded PVC insulation
Polyester tape
Tinned copper earthing wire, Al/PET tape
Black PVC sheath
This cable is used in chemical and petrochemical industry, powerplants, gas stations, water transportation systems,  instrumentation control and data processes, analog and digital signal transmission, dry or wet places.
Category: Tag:
  • Description

    Product Description

    İletken
    Kesiti
    İletken
    Direnci
    Ω/km (20 °C)
    İzolasyon
    Direnci MΩ/km (20 °C)
    Efektif
    Kapasite pF/m
    Endüktans/
    Direnç Oranı nH/Ω
    Akım Taşıma Kapasitesi A Çalışma Voltajı V DC Test Voltajı V (DC. 1 dakika)
    Cross
    Section
    Conductor
    Resistance
    Ω/km (20 °C)
    Insulation
    Resistance MΩ/km (20 °C)
    Mutual
    Capacitance
    pF/m
    Inductance/
    Resistance
    Ratio nH/Ω
    Current Carrying
    Capacity A
    Operating Voltage V DC Test Voltage V (DC. 1 minute)
    0.50 mm² 36 100 170 25 6 300/500 2000
    0.75 mm² 24,5 100 170 25 13 300/500 2000
    1.00 mm² 18,1 100 170 25 16 300/500 2000
    1.30 mm² 13,9 100 170 40 18 300/500 2000
    1.5 mm² 12,1 100 170 40 20 300/500 2000
    2.5 mm² 7,41 100 170 60 25 300/500 2000
    Bükülme Yarıçapı Sıcaklık Aralığı
    Bending Radius Temperature Range
    7.5xD mm -30°C~+70°C
  • Additional information

    Additional Information

    Certificates

    Trial